Sign In | Join Free | My portofva.com |
|
Categories | Telecom Battery |
---|---|
Brand Name: | Topband |
Model Number: | TB4850F-T110C |
Certification: | MSDS,CE |
Place of Origin: | China |
MOQ: | 50pcs |
Supply Ability: | 450Mwh/year |
Delivery Time: | 2~4weeks for samples; 4~6weeks for mass production |
Packaging Details: | standard export carton |
Price: | Negotiable |
Payment Terms: | L/C, T/T |
Nominal Voltage: | 48V |
Typical Capacity: | 50Ah |
Nominal Charge Voltage: | 58.4V |
Discharge Cut-off Voltage: | 40V |
Max Charge Current: | 50A |
Max Continuous Discharge Current: | 50A |
Peak Discharge Current: | 100A |
Work Temperature: | -20℃ - 60℃ ( -4℉ - 140℉ ) |
Cycles Life@ 100% DOD: | ≥2000 |
Weight: | 30.5kg |
Dimension: | 425*482*133 mm |
Material: | Nano LiFePO4 |
1. General Information
This specification defines the performance of rechargeable LiFePO4 battery pack TB4850F-T110C manufactured by Shenzhen Topband Battery Co., Ltd, describes the type, performance, technical characteristics, warning and caution of the battery pack.
2. Specification
|
3. Electrical Characteristics & Test Condition
Testing Conditions: Ambient Temperature: 25±5℃; Huminity:45%~75%.
|
4. Circuit Protection
The batteries are supplied with a LiFePO4 Battery Management System (BMS)that can monitor and optimized each single prismatic cell during charge & discharge, to protect the battery pack overcharge, over discharge, short circuit. Overall, the BMS helps to ensure safe and accurate running.
Test item | Content | Criterion |
Over charge | Over-charge protection for each cell | 3.90±0.03V |
Over-charge release for each cell | 3.60±0.05V | |
Over-charge release method | Under the release voltage | |
Over discharge | Over-discharge protection for each cell | 2.30±0.05V |
Over-discharge release for each cell | 2.80±0.05V | |
Over-discharge release method | Charging | |
Over current | Discharge over current protection | 400±50A |
Protection delay time | 50~200ms | |
Over current release method | Release after 30s. | |
Over & Lower Temperature | Battery charge/discharge over temperature | Protection @65±5℃ |
Release @55±5℃ | ||
Battery charge lower temperature | Protection @-5±5℃ | |
Release @5±0℃ |