Sign In | Join Free | My portofva.com
portofva.com
Products
Search by Category
Home > Physical Measuring Instruments >

Variable Frequency AC Resonant Test System , High Voltage Test Set For UHV Substation Or GIS

Categories AC Resonant Test System
Brand Name: Fanke
Model Number: CHX-4800KVA/200KV,400KV,600KV,800KV
Certification: ISO9001
Place of Origin: CHINA
MOQ: One Set
Price: Negotiable
Payment Terms: L/C, T/T
Supply Ability: 5 sets / 2months
Delivery Time: 45~60 working days
Packaging Details: Export standard wooden case with fumigation free
Test Principle: Variable Frequency Resonant Circuit
Usage: On-site AC Withstand Voltage Test
Design Feature:: Highed Voltage Modular Test Reactor, Higher Q Value Output ,Multiple Test Range
Component:: V/F Power Source, Excitation Transformer,lighter Modular Test Reactor, And Voltage Divider
Test Frequency:: 30-300Hz
Duty Cycle: 15mints or 60 Mints
Test Accuracy: No Less Than 1.5%
Output Waveform: Good Sine Wave
Special For: On-site Test For UHV GIS , GIL , CT, PT
Test Standard:: IEC60060-1:2010;IEC 62271-203:2011 for GIS
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
  • Submit Buying Request
    • Product Details
    • Company Profile

    Variable Frequency AC Resonant Test System , High Voltage Test Set For UHV Substation Or GIS

    Variable Frequency Resonant Withstand Voltage Test Set , High Voltage Test Set For UHV Substation or GIS


    I. Application :


    This series of test system mainly aims at AC voltage withstand test of primary equipment of large capacitor and high voltage and can also satisfy field AC voltage withstand test of sorts of capacitance apparatus. HV test reactors use combined series-parallel patterns which not only meet the requirements of voltage withstand of HV transformer, GIS, SF6 breakers,mutual inductions and bushings but also that of long distance XLPE cables ,with compatibility of extensive tests to be a desired voltage withstand test device for power supply system overhauling and electric power engineer construction units.


    The above picture is for variable series resonance test system of 5000KVA/1000KV on test field in Shanxi Jindongnan Substation, testing HV
    GIS of 1000KV class UHV line in domestic.


    Applicable objects
    - Long distance XLPE cables with 110KV,220KV,500KV class
    - HV GIS or GIL, HV coupling capacitor,capacitor voltage transformer of no more than 1000KV class
    - Assembling capacitor(test frequency pledges in 45—65Hz)


    II. Main Components:(4000KVA/1000KV test system for example)


    SNName of ComponentsType and specificationQty.Each weightEach Dimension
    1Variable frequency powerFKVF-200kW/380V1piece180kgs750*700*1000mm
    2Excitation transformerCQSB(J)-200kVA1piece1800kgs650*650*800mm
    3HV resonant test reactorCHX(kf)-800kVA/200kV5pieces2800kgsD1200*H1250mm
    4Capacitive dividerTRF-1000kV/1000pF1set550kgsD350*H7600mm
    5Special test accessories1set

    Note:1.Load capacitantor can be optional when small load line is tesing or need analog load to control test frequency .

    2.Test reactor can be produced to be 150KV,200KV,250KV,300KV, 350KV, 400KV for each piece rated voltage according to different tested object scope or customer requried. The max. rated current of each HV reactor can be 1~15A optional in this serialized set,

    3. HV Damping inductance can be optional for suppressing high frequency harmonics and resisting overvoltage caused from tested object flashover, special in EHV or UHV test set.

    III. Test priciple :
    Portable Variable Frequency Resonant Withstand Voltage Test Set

    VF: Variable Frequency Power Source T : Excitation Transformer
    L : Test Reactor Cx: Tested Equipment MOA1: Lightning Arrestor
    C1,C2: Voltage divider(C1 is high voltage arm,C2 is low voltage arm )


    IV. General Technical Data:

    1. Mode of system test: Series resonant with variable frequency
    2. System model : CHX-4000KVA/200KV,400KV,600KV, 800KV,1000KV
    3. Input power supply : 380±10%(three-phase),50Hz/60Hz
    4. Number of HV test reactor: 4pieces
    5. Rated output capacity: 4000kVA
    6. Rated output Voltage: 200KV,400KV,600KV,800KV,1000KV
    7. Max Test voltage : no more than 200KV,400KV,600KV,800KV,1000KV
    8. Rated output current: 4A /single piece or in series;16A or 20A in parallal
    9. Reg. Freq range : 20Hz-300Hz
    10. Output Resonance voltage waveform: sine wave
    11. THD of output waveform: ≤1%
    12. Insulation level: Under 1.1 times and keeping 1min, normal
    13. Duty cycle : 60mints optional on under rated current working condition ;
    14. Quality factor of test set itself: Q≥60
    15. Temperature rise: Less than 65K under rated current working withn duty cycle;
    16. Noise level: No more than 70B
    17. Reactor Structure: oil immersed type, epoxy tube cylinder type;


    V. Technical Feature and advantage

    • Modular design, being able for series-parallel connection of reactors,wide range of application.
    • Operating frequency range:20-300Hz
    • High quality factor value:Q ≥ 100(when f=20Hz) large thermal capacity, low temperature rise, long
    • continuous of performance period
    • Convenient for field test for the size and weight smaller than conventional test transformers.
    • The output voltage waveform is sine wave, the waveform deviation factor ≤ 1%
    • This device can be furnished with special test vehicle and container together
    • PD free design optional.

    VI. Main Measuring and control software panel as following :


    Portable Variable Frequency Resonant Withstand Voltage Test Set


    VII.Accessories

    • Accessory box for storage accessoires
    • Input cables of power source
    • Output cables of power source
    • Output cables of exciting transformer
    • System grounding cables
    • Parallel cables of the reactor
    • HV measuring cables ( the signal output cables of voltage divider )
    • HV output cables(reactor to divide,divider to test object)
    • Supporting base for divider
    • Corona ring for test reactor and divider
    • A final test report, a quality Certificate ,a user manual and a packing list are offered .


    VIII. Other Typical Model


    1 For 123KV ~300KV class GIS on-site AC hipot test


    ModelRated voltageRated output currentRated output capacity

    Application

    (From 45Hz starting)

    CHX-400KVA/200KV,400KV200KV*22A@200KV400KVAFor 123KV and below class GIS
    1A@400KVFor 300KV and below class GIS
    CHX-800KVA/200KV,400KV200KV*24A@200KV800KVAFor 123KV and below class GIS
    2A@400KVFor 300KV and below class GIS
    CHX-1000KVA/200KV,400KV200KV*25A@200KV1000KVAFor 123KV and below class GIS
    2.5A@400KVFor 300KV and below class GIS
    CHX-2000KVA/200KV,400KV200KV*210A@200KV2000KVAFor 123KV and below class GIS
    5A@400KVFor 300KV and below class GIS
    Special requirement can be made by order

    2 For 145KV ~362KV class GIS on-site AC hipot test


    ModelRated voltageRated output currentRated output capacity

    Application

    (From 45Hz starting)

    CHX-500KVA/250KV,500KV250KV*22A@250KV500KVAFor 145KV and below class GIS
    1A@500KVFor 362KV and below class GIS
    CHX-1000KVA/250KV,500KV250KV*24A@250KV1000KVAFor 145KV and below class GIS
    2A@500KVFor 362KV and below class GIS
    CHX-2000KVA/250KV,500KV250KV*28A@250KV2000KVAFor 145KV and below class GIS
    4A@500KVFor 362KV and below class GIS
    CHX-3000KVA/250KV,500KV250KV*212A@250KV3000KVAFor 145KV and below class GIS
    6A@500KVFor 362KV and below class GIS
    Special requirement can be made by order


    3 For 170KV ~550KV class GIS on-site AC hipot test


    ModelRated voltageRated output currentRated output capacity

    Application

    (From 45Hz starting)

    CHX-1200KVA/300KV,600KV300KV*24A@300KV1200KVAFor 170KV and below class GIS
    2A@600KVFor 550KV and below class GIS
    CHX-1800KVA/300KV,600KV300KV*26A@300KV1800KVAFor 170KV and below class GIS
    3A@600KVFor 550KV and below class GIS
    CHX-2400KVA/300KV,600KV300KV*28A@300KV2400KVAFor 170KV and below class GIS
    4A@600KVFor 550KV and below class GIS
    CHX-3600KVA/300KV,600KV300KV*212A@300KV3600KVAFor 170KV and below class GIS
    6A@600KVFor 550KV and below class GIS
    CHX-4800KVA/300KV,600KV300KV*216A@300KV4800KVAFor 170KV and below class GIS
    8A@600KVFor 550KV and below class GIS
    Special requirement can be made by order


    4 For 123KV ~800KV class GIS on-site AC hipot test


    ModelRated voltageRated output currentRated output capacity

    Application

    (From 45Hz starting)

    CHX-2400KVA/200KV×4800KV12A@200KV2400KVAFor 123KV and below class GIS
    6A@400KVFor 300KV and below class GIS
    3A@600KVFor 550KV and below class GIS
    3A@800KVFor 800KV and below class GIS
    CHX-3600KVA/200KV×4800KV13A@200KV3600KVAFor 123KV and below class GIS
    9A@400KVFor 300KV and below class GIS
    4.5A@600KVFor 550KV and below class GIS
    4.5A@800KVFor 800KV and below class GIS
    CHX-4800KVA/200KV×4800KV24A@200KV4800KVAFor 123KV and below class GIS
    12A@400KVFor 300KV and below class GIS
    6A@600KVFor 550KV and below class GIS
    6A@800KVFor 800KV and below class GIS
    Special requirement can be made by order

    IX. On-site insulation test standard table from IEC 62271-203:2011 for HV GIS

    Variable Frequency Resonant Withstand Voltage Test Set for long HV XLPE Cable

    Quality Variable Frequency AC Resonant Test System , High Voltage Test Set For UHV Substation Or GIS for sale
    Send your message to this supplier
     
    *From:
    *To: WUHAN FANKE HAIWO HIGH VOLTAGE TECHNOLOGY CO.,LTD.
    *Subject:
    *Message:
    Characters Remaining: (0/3000)
     
    Inquiry Cart 0

    Friendly Links: www.everychina.com

    Home| Products| Suppliers| Quality Suppliers| Site Map |About Us |Contact Us |Help |关于我们 |联系我们

    Copyright © 2009 - 2024 portofva.com. All rights reserved.